Panasonic 42PET1U6 Datasheet

Browse online or download Datasheet for Split-system air conditioners Panasonic 42PET1U6. Panasonic 42PET1U6 Data Sheet User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 3
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Split System Submittal Data
System: 42PET1U6 Indoor: S-42PT1U6 Outdoor: U-42PE1U6
Single Split System - Ceiling-Suspended Heat Pumps
Approval:
Date:
Construction:
Unit#:
Drawing#:
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
General Data
Power (V/P/Hz) 230/208/1/60
Circuit Ampacity (A) 15-40 Indoor-Outdoor
Fuse Size, Max.(A) 15-40 Indoor-Outdoor
Compressor DC Rotary Inverter
No. Used 1
R.L. Amps - L.R. (A) 18.1 - 31.0
Outdoor Unit
Fan type Propeller
Dia & Length (in.) - No. used 18-7/64-2
Type Drive - No. Speeds DC Motor
No. Poles (RPM) 8 - 830
No. Motors (W) 2 - 90
CFM (High) 3531
F.L. Amps (A) 19.7
Coil Type Aluminum Fin & Copper Pipe
Fin Type - Pipe Type Slit Plate - Inner Rifled
Rows - F.P.I. 2 - 12.7
Face Area (sq.ft.) 11.62
Tube Size (in) 3/8"
Indoor Unit
Fan type Centrifugal
Dia & Length (in.) - No. used 5-29/32-4
No. Speeds 3 & Auto
No. Poles (RPM, High) 4 - 1099
No. Motors (W) 1 - 100
CFM (HI/Med/Lo) 1130/950/775
Indoor Sound Rating (Hi) (dB-A) 44
F.L. Amps (A) 0.8
Coil Type
Aluminum Plate Fin & Copper Tube
Fin Type - Pipe Type Slit Plate - Inner Rifled
Rows - F.P.I. 3 - 14.9
Face Area (sq.ft.) 3.51
Tube Size (in) 9/32"
Drain Connection Size (in.) 1-1/4"
Refrigerant R410A
Lbs. - R410a 7.94
Control Electric Expansion Valve
Connection Flare
Line Length, Max (ft.) 165
Line Difference, Max (ft.) 50 (outdoor lower),
100 (outdoor higher)
Line Size (in. O.D. Discharge) 3/8"
Line Size (in. O.D. Suction) 5/8"
Dimensions (HxWxD)
Indoor Unit (Crated) (in.) 12-15/32 x 66-1/16 x 31-1/16
Indoor Unit (Uncrated) (in.) 9-7/16 x 62-1/32 x 26-3/8
Outdoor Unit (Crated) (in.) 52-3/8 x 39-31/32 x 6-3/32
Outdoor Unit (Uncrated) (in.) 48-7/16 x 37 x 13-3/8
Weight (lbs.)
(Indoor) Net 84
(Indoor) Shipping 97
(Outdoor) Net 220
(Outdoor) Shipping 240
(Indoor) Shipping Volume (cu.ft.) 14.8
(Outdoor) Shipping Volume (cu.ft.) 19.5
Page view 0
1 2 3

Summary of Contents

Page 1 - Split System Submittal Data

Split System Submittal DataSystem: 42PET1U6 Indoor: S-42PT1U6 Outdoor: U-42PE1U6Single Split System - Ceiling-Suspended Heat PumpsApproval:Date:Co

Page 2

Panasonic North AmericaAir Conditioning Division1690 Roberts Blvd., NW, Suite 110Kennesaw, GA 30144us.panasonic.com/airconFeaturesControls Microproces

Page 3 - Outdoor Dimensions

Panasonic North AmericaAir Conditioning Division1690 Roberts Blvd., NW, Suite 110Kennesaw, GA 30144us.panasonic.com/airconIndoor DimensionsOutdoor Dim

Comments to this Manuals

No comments