Panasonic KE36NKUA Datasheet

Browse online or download Datasheet for Split-system air conditioners Panasonic KE36NKUA. Panasonic KE36NKUA Data Sheet User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 3
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Split System Submittal Data
System: KE36NKU Indoor: CS-KE36NKU Outdoor: CU-36NKU
Wall Mounted Heat Pump
Approval:
Date:
Construction:
Unit#:
Drawing#:
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
General Data
Power (V/P/Hz) 230/208/1/60
Circuit Ampacity (A) 16.5-18.0
Fuse Size, Max.(A) 45
Compressor DC Twin Rotary (Inverter)
No. Used 1
R.L. Amps - L.R. (A) 20.0-31.0
Outdoor Unit
Fan Type Propeller
Dia (in.) - No. Speeds 19-9/32” Auto (Hi, Me, Lo)
Type Drive Direct / DC Motor
No. Poles (RPM) 8-750
No. Motors (W) 1-142
F.L. Amps (A) 19.6-21.5
Coil Type Aluminum Fin and Copper Pipe
Fin Type - Pipe Type Slit Plate - Inner Rifled
Rows - F.P.I. 2-21.2
Rows - F.P.I. 2 - 18.1
Face Area (sq.ft.) 8.05
Tube Size (in.) 3/8”
Indoor Unit
Fan Type Cross Flow
Dia (in.) 3-15/16” x 32”
No. Speeds Auto and 3 steps
No. Poles (RPM (Cool / Heat), High) 8-1,370 / 1,450
No. Motors (W) 47
CFM (Hi/Med/Low) Cooling 630/530/412
CFM (Hi/Med/Low) Heating 671/559/441
Operating Sound-Hi/Me/Lo/ dB-A
(Cool)
49 / 44 / 39
Operating Sound-Hi/Me/Lo/ dB-A
(Heat)
49 / 44 / 39
F.L. Amps 0.4
Coil Type
Aluminum Plate Fin & Copper Tube
Fin Type - Pipe Type Slit Plate - Inner Rifled
Rows - F.P.I. 2-19.5
Face Area (sq. ft.) 4.55
Tube Size (in.) 3/8”
Drain Connection Size (in.) 1-1/4”
Refrigerant R410A
Lbs. - R410a (outdoor unit) 6.5
Refrigerant Control Electronic Expansion Valve
Refrigerant Tubing Connections Flare
Line Length, Max (ft.) 165
Line Difference, Max (ft.) 50 (outdoor lower), 100 (outdoor
higher)
Line Size (in. O.D. Discharge) 3/8”
Line Size (in. O.D. Suction) 5/8”
Pre-charge, tubing length at
shipment
100’
Dimensions (HxWxD)
Indoor Unit (Crated) (in.) 12-7/32 x 44-7/8 x 14-31/32
Indoor Unit (Uncrated) (in.) 11-3/16 x 41-15/16 x 9-1/16
Outdoor Unit (Crated) (in.) 42-3/8 x 40 x 16-3/8
Outdoor Unit (Uncrated) (in.) 35-13/16 x 37-1/32 x 13-3/8
Weight (lbs.)
(Indoor) Net 32.0
(Indoor) Shipping 39.7
(Outdoor) Net 185.2
(Outdoor) Shipping 207.2
(Indoor) Shipping Volume (cu.ft.) 4.59
(Outdoor) Shipping Volume (cu.ft.) 15.88
Page view 0
1 2 3

Summary of Contents

Page 1 - Split System Submittal Data

Split System Submittal DataSystem: KE36NKU Indoor: CS-KE36NKU Outdoor: CU-36NKUWall Mounted Heat PumpApproval:Date:Construction:Unit#:Drawing#:Job

Page 2

FeaturesControls MicroprocessorRemote Controller LCD Wireless Type, Temp. Sensor Built InTemperature Control IC ThermistorTimer 24 Hour, Single Event,

Page 3 - Outdoor Dimensions

Panasonic North AmericaAir Conditioning Division1690 Roberts Blvd., NW, Suite 110Kennesaw, GA 30144us.panasonic.com/airconIndoor DimensionsOutdoor Dim

Comments to this Manuals

me 07 Feb 2024 | 15:00:39

thanks