Panasonic CZ-64ESMC1U Installation Manual Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 20
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
6
Electrical Wiring
Fig. 2
<Back side of system controller>
DC voltage pulse
Photocoupler input
Allowable contact voltage
and current: 24 V, 10 mA
Pulse width: 300 ms or
more
No-voltage a-contact
static output
Allowable contact voltage
and current: 30 V, 0.5 A
SYSTEM CONTROLLER
DC24V
COM
Digital
Input
A1
A2
A3
A4
A5
A6
When using the T10 cable:
(1) Connect B1, B2 to indoor unit 2P terminal base.
(*No polarity). Wire size is AWG#W18.
(2) Connect B5, B6 to indoor PCB T10 connector using the
accessory 6P connector. (with fuse) (*No polarity)
Total wire length is less than 330 ft. and size is
AWG#W18.
Fig. 3
When using the CRV cable:
(1) Connect B1, B2 to indoor unit 2P terminal base.
(*No polarity). Wire size is AWG#W18.
(2) Connect B5, B6 to indoor PCB CRV connector using the
accessory 2P connector. (*No polarity)
Total wire length is less than 330 ft. and size is
AWG#W18.
Fig. 4
NOTE
Connectors are different depending on the indoor unit PCB.
Select the cable according to the indoor unit PCB.
Use the T10 cable.
Use the CRV cable.
T10 connectorT10 cable
T10 connectorT10 cable
CRV connectorCRV cable
Terminals for remote monitoring
A1:
Input for turning on air conditioners concurrently.
A2:
Input for turning off air conditioners concurrently.
A3:
Common input for turning air conditioners on or off.
A4:
ON operation state indicator output.
A5:
Alarm indicator output.
A6:
Common indicator output.
Basic wiring
B1:
Inter-unit control wiring. (Low voltage)
B2:
To indoor unit 2P terminal base (U1, U2)
*No polarity
B3:
Auxiliary of inter-unit control wiring
B4:
Not be used
B5:
Power supply: DC 12 V *No polarity
B6:
To CRV connector or T10 connector on indoor PCB
CZ-64ESMC1U_eng.indd 6
CZ-64ESMC1U_eng.indd 6
2011/09/20 19:14:57
2011/09/20 19:14:57