Panasonic KE12NB41 Datasheet

Browse online or download Datasheet for Split-system air conditioners Panasonic KE12NB41. Panasonic KE12NB41 Data Sheet User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 3
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Split System Submittal Data
System: KE12NB41 Indoor: CS-KE12NB41 Outdoor: CU-KE12NK1
Ceiling Recessed Heat Pump
Approval:
Date:
Construction:
Unit#:
Drawing#:
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
General Data
Power (V/P/Hz) 115/1/60
Circuit Ampacity (A) 20
Fuse Size, Max.(A) 20
Compressor DC Twin Rotary (Inverter)
No. Used 1
R.L. Amps - L.R. (A) 9.8/10.6-20
Crankcase Heater (W) 20
Outdoor Unit
Fan Type Propeller
Dia (in.) - No. Speeds 15-3/4”-Auto(Hi and multi step)
Type Drive Direct / DC Motor
No. Poles (RPM) 8-750
No. Motors (W) 1-30
F.L. Amps (A) 0.6
Coil Type Aluminum Fin and Copper Pipe
Fin Type - Pipe Type Corrugated Plate - Inner Rifled
Rows - F.P.I. 2-18.1
Face Area (sq.ft.) 3.95
Tube Size (in.) 5/16”
Indoor Unit
Fan Type Turbo
Diameter and Depth 12-5/8” x 5-3/4”
No. Speeds Auto and 3 steps
No. Poles (RPM, High) 8-470 Cool / 520 Heat
No. Motors (W) 1-30
CFM (Hi/Med/Low) Cooling 235 / 206 / 194
CFM (Hi/Med/Low) Heating 268 / 247 / 224
Operating Sound-Hi/Me/Lo/ dB-A
(H-C)
44 / 40 / 36
F.L. Amps 0.346
Coil Type
Aluminum Plate Fin & Copper Tube
Fin Type - Pipe Type Slit Plate - Inner Rifled
Rows - F.P.I. 2-18.1
Face Area (sq. ft.) 2.94
Tube Size (in.) 9-32”
Drain Connection Size (in.) 23/32”
Refrigerant R410A
Lbs. - R410a (outdoor unit) 2.43
Refrigerant Control Electronic Expansion Valve
Refrigerant Tubing Connections Flare
Line Length, Max (ft.) 65’
Line Heigth Difference, Max (ft.) 23’
Line Size (in. O.D. Discharge) 1/4”
Line Size (in. O.D. Suction) 3/8”
Pre-charge, tubing length at
shipment
25’
Dimensions (HxWxD)
Indoor Unit (Crated) (in.) 11-13/32” x 24-13/16” x 28-1/8”
Indoor Unit (Uncrated) (in.) Body 11-5/32” x 22-5/8” x 22-5/8”
Indoor Unit (Uncrated) (in.) Body
and Panel
12-5/16” x 24-19/32” x 24-19/32”
Outdoor Unit (Crated) (in.) 23-5/8” x 33-11/16” x 14-1/4”
Outdoor Unit (Uncrated) (in.) 21-9/16” x 28-11/32” x 10-1/16”
Weight (lbs.)
(Indoor) Net 35.3
(Indoor) Shipping 41.9
(Outdoor) Net 77.2
(Outdoor) Shipping 83.8
(Indoor) Shipping Volume (cu.ft.) 4.59
(Outdoor) Shipping Volume (cu.ft.) 6.35
Page view 0
1 2 3

Summary of Contents

Page 1 - Split System Submittal Data

Split System Submittal DataSystem: KE12NB41 Indoor: CS-KE12NB41 Outdoor: CU-KE12NK1Ceiling Recessed Heat PumpApproval:Date:Construction:Unit#:Draw

Page 2

FeaturesControls MicroprocessorRemote Controller LCD Wireless Type, Temp. Sensor Built InTemperature Control IC ThermistorTimer 24 Hour, Single Event,

Page 3 - Outdoor Dimensions

Panasonic North AmericaAir Conditioning Division1690 Roberts Blvd., NW, Suite 110Kennesaw, GA 30144us.panasonic.com/airconIndoor DimensionsOutdoor Dim

Comments to this Manuals

No comments