Split System Submittal Data
Outdoor: CU-3KS19NBU
MultiSystem - Outdoor
Approval:
Date:
Construction:
Unit#:
Drawing#:
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
General Data
Power (V/P/Hz) 208/230/1/60
Circuit Ampacity (A) 15
Fuse Size, Max.(A) 20
Compressor DC Twin Rotary
No. Used 1
R.L. Amps - L.R. (A) 7.0 - 13.0
Crankcase Heater (A) N/A
Outdoor Unit
Fan Type Propeller
Dia & Length (in.) - No. Speeds D18-1/8 - 1
Type Drive - No. Speeds DC Motor
No. Poles (RPM) 8 - (750)
No. Motors (W) 1-(90)
CFM (High) 1707
F.L. Amps (A) 0.45
Coil Type Aluminum Fin & Copper Pipe
Fin Type - Pipe Type Corrugated Plate - Inner Riffeled
Rows - F.P.I. 2 - 18.1
Face Area (sq.ft.) 6.4
Tube Size (in) 3/8”
Refrigerant R410A
Lbs. - R410a 6.17
Control Electronic Expansion Valve
Line Size (in. O.D. Discharge) 1/4” x 3 (Flare)
Line Size (in. O.D. Suction) 3/8” x 3 (Flare)
Dimensions (HxWxD)
Indoor Unit (Crated) (in.) 33-27/32 x 40-5/8 x 16-1/4
Indoor Unit (Uncrated) (in.) 29-1/8 x 35-7/16 x 12-19/32
Weight (lbs.)
Net 138.9
Shipping 147.7
Shipping Volume (cu.ft.) 12.71
Performance Data @ ARI Standard Conditions (230/208V)
Cooling
Total Capacity (BTU/H) 18,800 (9,800 - 18,800)
Sensible Capacity (BTU/H) 16,000
Latent Capacity (BTU/H) 2,800
SEER 18.0
Amps (A) 7.0
Max. Amps (A) 13
Power Inputs (KW) 1,570
Max. Inputs (W) 3,000
Outdoor Sound Rating (dB-A) 50
Operating Range
Indoor Air Intake Temp
Outdoor Air Intake Temp
Cooling (Max) 95F DB/71F WB 115 F DB
Cooling (Min) 67 DB/57F WB 14 F DB