[Intake Air Temp. - Remote Controller Setting Temp.] >
[Thermostat-OFF Temp. +0.5 °C]
Operated in corresponding frequency.
Frequency is decided after a completion of the starting
control (in 60 seconds).
When Room Temp. is below [Thermostat-OFF Temp.]
continuously for 3 minutes or more, it turns to Thermostat-
OFF operation.
When room temperature almost comes to Thermostat-OFF
Temp., the operation turns to the Minimum power & fan
speed: SSLo.
[Intake Air Temp. - Remote Controller Setting Temp.] >
[Thermostat-OFF Temp. +0.5 °C]
Operated in corresponding frequency.
Frequency is decided after a completion of starting control
(in 60 seconds).
When Room Temp. is below Thermostat-OFF Temp.
continuously for 3 minutes or more, it turns to Thermostat-
OFF operation.
When room temperature almost comes to Thermostat-OFF
Temp., the operation turns to the Maximum power.
Dry Power TE9DKE TE12DKE
Intake Air Temp.
Difference (°C)
Maximum 2.7kW 4.0kW
Rated 2.5kW 3.6kW
Intermediate ~ ~
Minimum 0.8kW 0.8kW
(-2.50) OFF
Heating Power TE9DKE TE12DKE
Intake Air Temp.
Difference (°C)
OFF
Minimum 0.8kW 0.8kW
Intermediate ~ ~
Rated 3.5kW 4.5kW
(+1.00) Maximum 4.6kW 6.2kW
9.3.2. Dry Operation
9.3.2.1. Thermostat Control
9.3.3. Heating Operation
9.3.3.1. Thermostat Control