9.12. Protection Control
9.12.1. Time Delay Safety Control
1. The compressor will not start for two minutes after stop of operation.
2. This control is not applicable if the power supply is cut off and on again or after 4-way valve deices condition.
9.12.2. 30 Seconds Forced Operation
1. Once the compressor starts operation, it will not stop its operation for 30 minutes.
2. However, it can be stopped by using remote control or Auto Switch at indoor unit.
* The other Protection controls are shown in “9.3.2 Protection Control from Overload Cooling & Dry Operation” and “9.3.3
Protection Control from Overload Heating Operation“.